Rm-materials-handling VARIABLE SPEED CONTROLS ControlMaster NXT Service Manuale Utente Pagina 48

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 53
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 47
R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325
-
5319
48/53
R&M Materials Handling, I
X
Blink
Seven
times
7
X OFF
Other fault
Note: There is a pause after each time the green LED has finished blinking the error code sequence. After the pause, the
green LED starts blinking again.
The warning and fault code numbers and corresponding warnings and faults, possible causes and suggested
solutions are listed in the following table.
Code Warning or Fault Possible cause Solution
1
Over current / current
limit (stall)
A sudden and significant load increase
has occurred
There is a short circuit in the motor cable
The motor is inadequate for the
application
The motor parameters have been set
wrong
Current limit activates
Ramp time is too short
Check the load of the motor
Check the motor brake operation
Check the connection of the motor cable
Check the motor insulation
Verify the correct parameters
Check crane/trolley runway clearness
To reset: Power off and restart after 1 min.
2
Power supply under- or
over voltage, over
voltage at start
The supply voltage is below 240VAC
The supply voltage is unbalanced
The deceleration time is too short
The supply voltage is over 528 VAC
(480V+10%), has over voltage spikes or
not sinusoidal wave form
Check that the supply voltage is not
unbalanced
Check that the supply voltage level is
above 380VAC-15%. Use, for example,
autotransformer to boost the voltage
Set a longer deceleration time
Measure the supply voltage level and
wave form, use an autotransformer to
lower the voltage
Check the braking resistor cable (model
006, not 003)
Check the braking resistor type and
resistance (internal 120, external 90)
To reset: voltage must increase above the
limit OR power off and restart after 1 min.
Main voltage must be under 528 V
AC
3
Frequency converter
Under / over temperature
The crane is operated in a temperature
that is too low/high
The cubicle/panel heating is not working
The cubicle/panel isolation is broken or
the door is open
The cubicle/panel cooling is not working
Dust inside the frequency converter
Broken cooling fan
Check that the environment temperature
meets the crane’s requirements
Check the cubicle/panel heating/cooling
systems and air flow. If cooling fan is not
working replace the frequency converter.
To reset: when the ambient temperature
rises above -10˚C OR drops below +40˚C.
4
Earth fault in motor
output
The motor load is not symmetric
There is an insulation failure in the motor
winding or motor cable
Check the motor/motor cable insulation
(phase-ground, phase-phase)
To reset: power off and restart after 1 min
5
External stop / limit
warning
Limit switch is activated
The motor has overheated
Loose or missing wire in DI6
Parameter S5 setting
Drive back from limit switch
Wait until the motor is cooled down
To reset: Power off and restart after 1 min.
6
DC bus over voltage
DC bus voltage has been too high
because of too short slowdown ramp time
The tailwind load is too high or, in tandem
use, the other crane is pushing
Check the braking resistor connection
Increase the deceleration ramp time
(Switch group S3)
To reset: leave the controls at a neutral
position at least 0.5 second
Vedere la pagina 47